Randamente de energie electrică ale autotransformatoarelor/transformatoarelor FIT/MT din rețeaua electrică de transport
T_max = 4380h, cos phi = 0,9, tau = 2628h, k_u = 0.5,
200 MVA
231/121/10kV
AT
existente
AT
performante
Delta P0=
105
kW
Delta P0=
45
kW
S/Sn
Delta Pscc=
495
kW
Delta Pscc=
350
kW
0,3
99,56
99,80
0,5
99,68
99,84
0,8
99,72
99,84
T_max = 5256h, cos phi = 0,9, tau = 3574h, k_u = 0.6
200 MVA
231/121/10kV
AT
existente
AT
performante
Delta P0=
105
kW
Delta P0=
45
kW
S/Sn
Delta Pscc=
495
kW
Delta Pscc=
350
kW
0,3
99,62
99,84
0,5
99,71
99,86
0,8
99,73
99,85
T_max = 7008h, cos phi = 0,9, tau = 5887h, k_u = 0.8
200 MVA
231/121/10kV
AT
existente
AT
performante
Delta P0=
105
kW
Delta P0=
45
kW
S/Sn
Delta Pscc=
495
kW
Delta Pscc=
350
kW
0,3
99,69
99,85
0,5
99,74
99,86
0,8
99,72
99,83
T_max = 4380h, cos phi = 0,9, tau = 2628h, k_u = 0.5,
250 MVA
400/121/20kV
TR
existente
TR
performante
Delta P0=
190
kW
Delta P0=
85
kW
S/Sn
Delta Pscc=
850
kW
Delta Pscc=
500
kW
0,3
99,37
99,71
0,5
99,55
99,78
0,8
99,61
99,80
T_max = 5256h, cos phi = 0,9, tau = 3574h, k_u = 0.6
250 MVA
400/121/20kV
TR
existente
TR
performante
Delta P0=
190
kW
Delta P0=
85
kW
S/Sn
Delta Pscc=
850
kW
Delta Pscc=
500
kW
0,3
99,45
99,74
0,5
99,59
99,80
0,8
99,62
99,80
T_max = 7008h, cos phi = 0,9, tau = 5887h, k_u = 0.8
250 MVA
400/121/20kV
TR
existente
TR
performante
Delta P0=
190
kW
Delta P0=
85
kW
S/Sn
Delta Pscc=
850
kW
Delta Pscc=
500
kW
0,3
99,55
99,79
0,5
99,63
99,81
0,8
99,61
99,79
T_max = 4380h, cos phi = 0,9, tau = 2628h, k_u = 0.5,
400 MVA
AT
existente 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 231/121/10 kV
Delta P0=
320
kW
Delta P0=
105
kW
Delta P0=
70
kW
Delta P0=
60
kW
Delta P0=
60
kW
S/Sn
Delta Pscc=
1060
kW
Delta Pscc=
860
kW
Delta Pscc=
490
kW
Delta Pscc=
510
kW
Delta Pscc=
660
kW
0,3
99,35
99,76
99,85
99,86
99,86
0,5
99,56
99,81
99,88
99,88
99,88
0,8
99,64
99,81
99,89
99,89
99,87
T_max = 5256h, cos phi = 0,9, tau = 3574h, k_u = 0.6
400 MVA
AT
existente 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 231/121/10 kV
Delta P0=
320
kW
Delta P0=
105
kW
Delta P0=
70
kW
Delta P0=
60
kW
Delta P0=
60
kW
S/Sn
Delta Pscc=
1060
kW
Delta Pscc=
860
kW
Delta Pscc=
490
kW
Delta Pscc=
510
kW
Delta Pscc=
660
kW
0,3
99,45
99,79
99,86
99,88
99,87
0,5
99,60
99,82
99,89
99,90
99,88
0,8
99,65
99,81
99,89
99,89
99,87
T_max = 7008h, cos phi = 0,9, tau = 5887h, k_u = 0.8
400 MVA
AT
existente 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 400/231/20 kV
AT
performante 231/121/10 kV
Delta P0=
320
kW
Delta P0=
105
kW
Delta P0=
70
kW
Delta P0=
60
kW
Delta P0=
60
kW
S/Sn
Delta Pscc=
1060
kW
Delta Pscc=
860
kW
Delta Pscc=
490
kW
Delta Pscc=
510
kW
Delta Pscc=
660
kW
0,3
99,56
99,82
99,88
99,89
99,88
0,5
99,65
99,83
99,89
99,90
99,88
0,8
99,66
99,79
99,88
99,88
99,85
T_max = 6000h, cos phi = 0,9
tau = 2628h, k_u = 0.5
500 MVA
400/231/22 kV
AT
existente
Delta P0=
110
kW
S/Sn
Delta Pscc=
720
kW
0,3
99,81
0,5
99,85
0,8
99,86
tau = 3574h, k_u = 0.6
AT
existente
Delta P0=
190
kW
Delta Pscc=
850
kW
99,45
99,59
99,62
tau = 5887h, k_u = 0.8
AT
existente
Delta P0=
190
kW
Delta Pscc=
850
kW
99,45
99,59
99,62